Error Code: EH C3 – Refrigerant Sensor is Out of Range

Modified on Thu, 22 May at 3:52 PM

Error Code: EH C3 – Refrigerant Sensor is Out of Range


What this means:
This error is triggered when the indoor unit receives no feedback from the refrigerant sensor for 150 seconds, or when it receives a fault signal for 10 seconds. It means the sensor is out of range or not responding at allTS36.


Try this first (quick reset):

  1. Turn off the system power completely.

  2. Wait 2 full minutes.

  3. Turn the unit back on and check the display.

  • If the error clears — monitor to ensure it doesn’t return.

  • If the error returns — begin checking the sensor and its wiring.


Next steps (for technicians):

  1. Inspect wiring between refrigerant sensor and indoor PCB:

    • Ensure all wires are properly connected.

    • Repair or reseat any loose connections.

  2. If wiring is correct and the issue remains:

    • Replace the refrigerant sensor.

  3. If replacing the sensor does not resolve the issue:

    • Replace the indoor main PCB.


What you might need:

  • Refrigerant sensor

  • Indoor main PCB

  • Connection wires


Helpful tip:
This fault is often misdiagnosed as a refrigerant leak, but EH C3 specifically indicates a sensor signal problem — not a confirmed leak. Always check wiring before replacing components.