Error Code: EH C2 – Refrigerant Sensor is Out of Range and Leakage is Detected
What this means:
This error occurs when the refrigerant sensor simultaneously detects:
A refrigerant concentration that exceeds 10% LFL for 10 seconds, or
A sudden spike to ≥20% LFL,
while also returning a sensor voltage that is out of normal range — indicating possible sensor malfunction or circuit faultTS37.
Try this first (quick reset):
Turn off power to the unit.
Wait 2 full minutes.
Turn the unit back on and observe if the error clears.
If the error clears — the system resumes monitoring.
If the error returns — follow the steps below.
Next steps (for technicians):
Check for system blockages:
Clear any blockages found before proceeding.
Inspect for refrigerant leaks:
If a leak is found → repair and recharge refrigerant.
If no leak is found → inspect refrigerant sensor wiring and communication signal integrity.
Multi-zone behavior:
The indoor unit detecting the leak sounds a buzzer for 10 seconds to 5 minutes.
Other zones only display ECC1 without a buzzer.
Buzzer can be silenced with any key press (remote, app, or wall controller).
What you might need:
Leak detection tools
Refrigerant
Wiring repair tools
Helpful tip:
EH C2 combines sensor range failure and refrigerant leak detection. Even if a leak is present, the error also flags a possible sensor voltage issue — so don’t overlook signal testing.