Error Code: EH 60 – Indoor Room Temperature Sensor (T1) Error
What this means:
The system has detected that the T1 sensor, which monitors the room temperature, is either open-circuited or short-circuited. This triggers an error when the sensor’s voltage drops below 0.06V or rises above 4.94VTS23.
Try this first (quick reset):
Turn off the power to the system.
Wait 2 minutes.
Turn the system back on and check the display.
If the error clears — it may have been a temporary signal issue.
If the error remains — proceed with sensor testing.
Next steps (for technicians):
Check the wiring between T1 sensor and PCB:
If not properly connected → reseat or repair the wires.
Measure the resistance of the T1 sensor:
If the resistance is not within range → replace the T1 sensor.
If the sensor and wiring are fine but the error persists:
Replace the indoor PCB.
What you might need:
T1 temperature sensor
Indoor PCB
Connection wires
Helpful tip:
EH 60 is part of a common group of sensor voltage faults. Always test both voltage and resistance before concluding component failure.