Error Code: EH 60 – Indoor Room Temperature Sensor (T1) Error

Modified on Thu, 22 May at 3:51 PM

Error Code: EH 60 – Indoor Room Temperature Sensor (T1) Error


What this means:
The system has detected that the T1 sensor, which monitors the room temperature, is either open-circuited or short-circuited. This triggers an error when the sensor’s voltage drops below 0.06V or rises above 4.94VTS23.


Try this first (quick reset):

  1. Turn off the power to the system.

  2. Wait 2 minutes.

  3. Turn the system back on and check the display.

  • If the error clears — it may have been a temporary signal issue.

  • If the error remains — proceed with sensor testing.


Next steps (for technicians):

  1. Check the wiring between T1 sensor and PCB:

    • If not properly connected → reseat or repair the wires.

  2. Measure the resistance of the T1 sensor:

    • If the resistance is not within range → replace the T1 sensor.

  3. If the sensor and wiring are fine but the error persists:

    • Replace the indoor PCB.


What you might need:

  • T1 temperature sensor

  • Indoor PCB

  • Connection wires


Helpful tip:
EH 60 is part of a common group of sensor voltage faults. Always test both voltage and resistance before concluding component failure.


Click here to view the detailed guide.TS23