Error Code: PC 02 – Compressor Top or IPM Temperature Protection
Applies to LETO and AURA Series
What this means:
This error indicates that the Intelligent Power Module (IPM) or the compressor has overheated. If the IPM temperature exceeds a safe limit, the system will shut down to prevent damage.
Try this first (quick check):
Turn off power to the system completely.
Wait 2 full minutes.
Turn the system back on and check the display.
If the error clears — the system may have overheated temporarily.
If the error returns — continue with the inspection steps below.
Next steps (for technicians):
Check the screws and mounting between the IPM module and its radiator (heatsink):
If screws are loose or missing, tighten and apply thermal grease.
Ensure the IPM has solid thermal contact for proper heat dissipation.
If mounting is correct but the error persists:
Replace the outdoor PCB.
What you might need:
IPM module board
Outdoor PCB
High-pressure protector
Connection wires
Thermal grease
Helpful tip:
Overheating can also result from restricted airflow, refrigerant overcharge, or system blockages. Always inspect airflow paths and pressure levels when this error appears.