Error Code: EH 3A – External Fan DC Bus Voltage is Too Low Protection
What this means:
This error occurs when the indoor unit receives a DC bus voltage signal from the external fan module that is abnormally low, or if the unit receives no feedback for over 150 seconds. It indicates a communication or power supply issue between the indoor PCB and the external fan moduleTS35.
Try this first (quick reset):
Shut off the power supply to the unit.
Wait 2 minutes.
Turn the system back on and check the display.
If the error clears — the system may have stabilized.
If the error remains — proceed with the troubleshooting steps below.
Next steps (for technicians):
Check the ENC1 setting:
If incorrect → reset ENC1 to factory specification.
If ENC1 is correct but error remains:
Replace the indoor main PCB.
What you might need:
Indoor main PCB
Helpful tip:
EH 3A is closely related to EH bA and EH 3b. All three relate to voltage or communication faults with the external fan module. Always confirm ENC1 settings before proceeding to PCB replacement.