Error Code: EC 56 – Indoor Coil Outlet Temperature Sensor (T2B) Error

Modified on Thu, 22 May at 3:46 PM

Error Code: EC 56 – Indoor Coil Outlet Temperature Sensor (T2B) Error


What this means:
This error occurs when the T2B sensor (which monitors the outlet temperature of the indoor coil) is either short-circuited, open-circuited, or providing an abnormal voltage reading. The system will shut down when the sampling voltage falls below 0.06V or above 4.94V.


Try this first (quick reset):

  1. Turn off the power to the unit completely.

  2. Wait 2 full minutes.

  3. Turn the unit back on and check if the error clears.

  • If the error clears — it may have been a temporary sensor glitch.

  • If the error remains — continue below.


Next steps (for technicians):

  1. Inspect the sensor wiring:

    • Make sure the T2B sensor is properly connected to the indoor PCB.

    • If wires are loose or damaged → repair or replace them.

  2. Measure sensor resistance:

    • If resistance is outside of the expected range → replace the T2B sensor.

    • If within spec and error still shows → replace the indoor PCB.


What you might need:

  • T2B sensor

  • Indoor PCB

  • Connection wires


Helpful tip:
Sensor-related faults like EC 56 are usually resolved by correcting wiring issues or replacing the sensor. Always test resistance before replacing the PCB.


Click here to view the detailed guide.TS18