Error Code: EC 5A – Failure of Enthalpy Inlet Temperature Sensor
What this means:
The enthalpy inlet temperature sensor is returning an abnormal voltage — either below 0.06V or above 4.94V. This indicates an open or short circuit, or a failed sensor. The system shuts down to protect itself from operating with inaccurate airflow or humidity temperature data.
Try this first (quick reset):
Turn off power to the unit completely.
Wait 2 full minutes.
Turn the unit back on and check the display.
If the error clears — the issue may have been temporary.
If the error remains — continue with the steps below.
Next steps (for technicians):
Check the sensor wiring to the PCB:
Ensure the enthalpy inlet temperature sensor is properly connected.
If loose or damaged → repair or replace the connection wires.
Measure the resistance of the sensor:
If resistance is outside the normal range → replace the sensor.
If resistance is normal but the error persists → replace the PCB.
What you might need:
Enthalpy inlet temperature sensor
Connection wires
Indoor PCB
Helpful tip:
This sensor helps control system efficiency in variable humidity and airflow conditions. It is especially critical in energy-saving or high-precision systems.