Error Code: PC 0L – Low Ambient Temperature Protection
Applies to LETO and AURA Series (select models)
What this means:
The outdoor temperature has dropped too low for the system to operate safely. To prevent damage, the unit enters protection mode and shuts down.
When this happens:
If the compressor is off and the outdoor temperature (T4) drops below -35°C for 10 seconds, the system will stop and display this error.
If the compressor is on and T4 drops below -40°C for 10 seconds, the same shutdown will occur.
Once the outdoor temperature rises above -32°C for at least 10 seconds, the system will automatically exit protection mode and resume operation.
What you can do:
Wait until the outdoor temperature rises to a safe level (above -32°C).
Once it does, the unit should recover on its own — no reset is needed.
If the error persists under normal temperatures, have a technician inspect the T4 sensor and control board.
What you might need (if issue continues in mild temperatures):
Outdoor ambient temperature sensor (T4)
Outdoor PCB (if logic fault exists)
Helpful tip:
This protection is common in extremely cold climates to avoid compressor damage. If your area frequently hits these low temperatures, consider pre-heaters or a cold-weather kit to reduce shutdowns.
Was this article helpful?
That’s Great!
Thank you for your feedback
Sorry! We couldn't be helpful
Thank you for your feedback
Feedback sent
We appreciate your effort and will try to fix the article