Error Code: PC 00 – Outdoor IPM Module Protection
Applies to LETO and AURA Series
What this means:
The outdoor unit’s IPM (Intelligent Power Module) has detected an abnormal voltage signal going to the compressor. As a safety precaution, the system shuts down to prevent further damage.
Try this first (easy fix):
Turn off power to the system completely.
Wait 2 full minutes.
Turn it back on and check if the error has cleared.
If the error is gone — the issue may have been temporary.
If it returns — proceed with the steps below.
Next steps (for technicians):
Check wiring between the PCB and compressor.
If wiring is loose or damaged, correct or replace it.
Check IPM terminal resistance:
If resistance is uneven, replace the IPM board or the outdoor PCB.
Check outdoor fan and ventilation:
If the fan isn’t working or the unit is poorly ventilated, correct the issue.
If necessary, refer to “Fan speed out of range” troubleshooting.
Check compressor resistance:
If resistance readings are off, replace the compressor.
Check IPM installation:
Ensure the module is properly installed, screws are tightened, and thermal grease is applied.
What you might need:
IPM module board
Outdoor PCB
Outdoor fan assembly
Compressor
Connection wires
Helpful tip:
This error may appear intermittently at first but can lead to full shutdown if left unresolved. Always verify IPM board health and compressor resistance before replacing parts.