Error Code: PC 43 – Outdoor Compressor Lack Phase Protection
What this means:
This error is triggered when the system detects an imbalance in the three-phase current of the compressor — especially if one or more phases show zero or near-zero current. This suggests a loss of phase, wiring fault, or compressor failureTS39.
Try this first (quick reset):
Power off the unit.
Wait at least 2 minutes.
Restart and observe the error display.
If the error clears — system resumes normal operation.
If the error remains — follow the diagnostic steps.
Next steps (for technicians):
Check compressor three-phase output wiring:
Look for visible disconnections or broken wires.
Inspect both ends of the compressor connecting line:
If connections are loose → correct them.
If all are good → proceed.
Check compressor winding resistance:
Measure resistance across all three phases.
If not symmetrical → replace the compressor.
If resistance is normal but issue persists:
Replace the outdoor main PCB.
What you might need:
Compressor
Outdoor PCB
Connection wires
Helpful tip:
Always verify three-phase balance before replacing components. A small variation is acceptable, but one phase reading zero usually means a disconnected or broken lead.